| Severity | Isolated | Pattern | Widespread |
|---|---|---|---|
| Immediate jeopardy | J· | K1 | L1 |
| Actual harm | G1 | H· | I· |
| Potential harm | D34 | E22 | F16 |
| Minimal | A· | B· | C5 |
CMS publishes about the three most recent standard surveys plus complaint and infection-control inspections from the prior three years. Older findings leave the dataset; their absence is not evidence they never happened.
Federal certification and the state license are different records. A nursing home is licensed by the state and, separately, certified by CMS to bill Medicare and/or Medicaid. We link them by the CCN when the state publishes it; otherwise by exact address, house number and street, or exact name within the same ZIP, and label that link as inferred. Never by name alone.
| Date | Domain | Survey types | Citations | Most severe | Open | |
|---|---|---|---|---|---|---|
| Feb 6, 2026 | Fire safety | Fire Safety Standard | 18 | Potential harm | — | Open → |
| Feb 6, 2026 | Health | Health Standard | 7 | Potential harm | — | Open → |
| Dec 4, 2024 | Fire safety | Fire Safety Standard | 23 | Potential harm | — | Open → |
| Dec 4, 2024 | Health | Health Complaint, Health Standard | 16 | Immediate jeopardy | — | Open → |
| Feb 24, 2023 | Fire safety | Fire Safety Standard | 13 | Potential harm | — | Open → |
| Feb 24, 2023 | Health | Health Standard | 3 | Potential harm | — | Open → |
| Date | Type | Amount | Payment denial | Record |
|---|---|---|---|---|
| Dec 4, 2024 | Civil money penalty (fine) | $132,948 | — | 335658|Fine|22362 |
| Severity | Isolated | Pattern | Widespread |
|---|---|---|---|
| Immediate jeopardy | J· | K1 | L1 |
| Actual harm | G1 | H· | I· |
| Potential harm | D34 | E22 | F16 |
| Minimal | A· | B· | C5 |
| Date | Tag | Deficiency | Scope / severity | Correction | Flags |
|---|---|---|---|---|---|
| Feb 6, 2026 | K-0133 | Install a two-hour-resistant firewall separation. Construction Deficiencies · Environment & life safety | D · Potential harm Isolated | Corrected Apr 24, 2026 | |
| Feb 6, 2026 | K-0211 | Keep aisles, corridors, and exits free of obstruction in case of emergency. Egress Deficiencies · Environment & life safety | D · Potential harm Isolated | Corrected Apr 3, 2026 | |
| Feb 6, 2026 | K-0223 |
“Corrected” does not erase a citation: the historical finding stays listed with its disposition. Narrative statements of deficiencies are not part of the CMS dataset; see Care Compare for the official inspection report.
CMS ratings apply to CMS-certified nursing homes only and are relative within each state. They are not a guarantee of any individual resident’s experience.
CMS legal business name of the certified provider. Operates this facility only.
Not part of a CMS-reported chain.
| Name | Type | Role (Carefield group) | CMS role text | Share | Since |
|---|---|---|---|---|---|
| Mary Ellen Bloodgood | Individual | Operational / managerial control | MANAGING CONTROL - GOVERNING BODY | not provided | Sep 1, 2022 |
| Matt Duso | Individual | Operational / managerial control | MANAGING CONTROL - GOVERNING BODY | not provided | Sep 1, 2022 |
| Elaine Haukenes | Individual | Operational / managerial control | MANAGING CONTROL - GOVERNING BODY | not provided | Sep 1, 2022 |
| Michael Smith | Individual | Operational / managerial control | MANAGING CONTROL - GOVERNING BODY | not provided | Sep 1, 2022 |
| Jean Wannal | Individual | Operational / managerial control | MANAGING CONTROL - GOVERNING BODY | not provided | Sep 1, 2022 |
| David Wissink | Individual | Operational / managerial control | MANAGING CONTROL - GOVERNING BODY | not provided | Sep 1, 2022 |
| Richard Williams | Individual | Operational / managerial control | OPERATIONAL/MANAGERIAL CONTROL | not provided | Dec 13, 2024 |
| Mary Ellen Bloodgood | Individual | Corporate officer / director | CORPORATE DIRECTOR | not provided | Sep 1, 2022 |
| Matt Duso | Individual | Corporate officer / director | CORPORATE DIRECTOR | not provided | Sep 1, 2022 |
| Elaine Haukenes | Individual | Corporate officer / director | CORPORATE DIRECTOR | not provided | Sep 1, 2022 |
| Lee Shurtleff | Individual | Corporate officer / director | CORPORATE DIRECTOR | not provided | Sep 1, 2022 |
| Michael Smith | Individual | Corporate officer / director | CORPORATE DIRECTOR | not provided | Sep 1, 2022 |
| Jean Wannal | Individual | Corporate officer / director | CORPORATE DIRECTOR | not provided | Sep 1, 2022 |
| David Wissink | Individual | Corporate officer / director | CORPORATE DIRECTOR | not provided | Sep 1, 2022 |
| Patrick Deptula | Individual | Corporate officer / director | CORPORATE OFFICER | not provided | Sep 1, 2022 |
| Lee Shurtleff | Individual | Corporate officer / director | CORPORATE OFFICER | not provided | Sep 1, 2022 |
| David Wissink | Individual | Corporate officer / director | CORPORATE OFFICER | not provided | Sep 1, 2022 |
| Darshan Patel | Individual | Managing employee | CONTRACTED MANAGING EMPLOYEE | not provided | Jan 1, 2018 |
| Patrick Deptula | Individual | Managing employee | W-2 MANAGING EMPLOYEE | not provided | Sep 1, 2022 |
| Richard Williams | Individual | Managing employee | W-2 MANAGING EMPLOYEE | not provided | Sep 1, 2022 |
| Mary Ellen Bloodgood | Individual | Trustee | TRUSTEE OF THE SNF | not provided | Sep 1, 2022 |
| Matt Duso | Individual | Trustee | TRUSTEE OF THE SNF | not provided | Sep 1, 2022 |
| Elaine Haukenes | Individual | Trustee | TRUSTEE OF THE SNF | not provided | Sep 1, 2022 |
| Lee Shurtleff | Individual | Trustee | TRUSTEE OF THE SNF | not provided | Sep 1, 2022 |
| Michael Smith | Individual | Trustee | TRUSTEE OF THE SNF | not provided | Sep 1, 2022 |
| Jean Wannal | Individual | Trustee | TRUSTEE OF THE SNF | not provided | Sep 1, 2022 |
| David Wissink | Individual | Trustee | TRUSTEE OF THE SNF | not provided | Sep 1, 2022 |
| Patrick Deptula | Individual | Additional disclosable party | ADP OF THE SNF | not provided | Dec 31, 2024 |
| Darshan Patel | Individual | Additional disclosable party | ADP OF THE SNF | not provided | Dec 31, 2024 |
| Richard Williams | Individual | Additional disclosable party | ADP OF THE SNF | not provided | Dec 31, 2024 |
Coordinates as published by CMS.
| Facility | Distance | Beds | CMS overall | Last inspection | Citations (window) | Fines |
|---|---|---|---|---|---|---|
| Kendal at Ithaca 2230 North Triphammer Road, Ithaca, NY 14850 CCN 335793 | 15 km | 48 | Dec 19, 2024 | 21 | — | |
| Cayuga Nursing and Rehabilitation Center 1229 Trumansburg Road, Ithaca, NY 14850 CCN 335249 | 19.1 km | 160 | Jan 24, 2025 | 521 IJ | $42k | |
| Beechtree Center for Rehabilitation and Nursing 318 South Albany Street, Ithaca, NY 14850 CCN 335017 | 19.7 km | 120 | Aug 29, 2025 | 43 | — | |
| Oak Hill Rehabilitation and Nursing Care Center 602 Hudson St, Ithaca, NY 14850 CCN 335225 | 19.7 km | 60 | Mar 19, 2025 | 37 | — |
| Source | Record | Facts | Evidence | Source release | Retrieved |
|---|---|---|---|---|---|
| CMS Provider Information US-CMS | 335658 | name, address, phone, certification, certified_beds, ownership_type, legal_business_name, chain | Verified | Oct 1, 2026 | Nov 7, 2026 |
| CMS Provider Information US-CMS | 335658 | ratings, staffing, health_survey_score Five-Star ratings and PBJ staffing apply to the CMS-certified universe only. | Verified | Oct 1, 2026 | Nov 7, 2026 |
| New York DOH Health Facility Information NY | 2550 | state_license, licensed_beds, licensee Linked to the CMS record by exact normalized street address and ZIP (the state roster does not publish the CCN). | Inferred | Oct 23, 2026 | Nov 7, 2026 |
| New York DOH Bed Certifications NY | 2550 | capacity, bed_certifications | Verified | Nov 1, 2026 | Nov 7, 2026 |
First seen by Carefield Nov 7, 2026 · last changed Nov 7, 2026. This record as JSON · Report a correction
| Provide exit doors that are held open by devices that will automatically close on the activation of a fire alarm or smoke detector. Egress Deficiencies · Environment & life safety |
| D · Potential harm Isolated |
| Corrected Apr 3, 2026 |
| Feb 6, 2026 | K-0281 | Install proper backup exit lighting. Egress Deficiencies · Environment & life safety | E · Potential harm Pattern | Corrected Apr 3, 2026 |
| Feb 6, 2026 | K-0291 | Install emergency lighting that can last at least 1 1/2 hours. Egress Deficiencies · Environment & life safety | D · Potential harm Isolated | Corrected Apr 23, 2026 |
| Feb 6, 2026 | K-0311 | Have an enclosure around a vertical opening shaft. Smoke Deficiencies · Environment & life safety | D · Potential harm Isolated | Corrected Apr 3, 2026 |
| Feb 6, 2026 | K-0321 | Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system. Smoke Deficiencies · Environment & life safety | E · Potential harm Pattern | Corrected May 8, 2026 |
| Feb 6, 2026 | K-0324 | Provide properly protected cooking facilities. Smoke Deficiencies · Environment & life safety | E · Potential harm Pattern | Corrected Apr 3, 2026 |
| Feb 6, 2026 | K-0345 | Have approved installation, maintenance and testing program for fire alarm systems. Smoke Deficiencies · Environment & life safety | F · Potential harm Widespread | Corrected Apr 3, 2026 |
| Feb 6, 2026 | K-0351 | Install an approved automatic sprinkler system. Smoke Deficiencies · Environment & life safety | D · Potential harm Isolated | Corrected Apr 27, 2026 |
| Feb 6, 2026 | K-0353 | Inspect, test, and maintain automatic sprinkler systems. Smoke Deficiencies · Environment & life safety | F · Potential harm Widespread | Corrected Apr 27, 2026 |
| Feb 6, 2026 | K-0511 | Have properly installed electrical wiring and gas equipment. Services Deficiencies · Environment & life safety | F · Potential harm Widespread | Corrected Apr 3, 2026 |
| Feb 6, 2026 | K-0531 | Have elevators that firefighters can control in the event of a fire. Services Deficiencies · Environment & life safety | F · Potential harm Widespread | Corrected Apr 3, 2026 |
| Feb 6, 2026 | K-0761 | To conduct inspection, testing and maintenance of fire doors by qualified individuals. Miscellaneous Deficiencies · Environment & life safety | F · Potential harm Widespread | Corrected Apr 3, 2026 |
| Feb 6, 2026 | K-0911 | Meet requirements for the installation and maintenance of electrical systems. Gas, Vacuum, and Electrical Systems Deficiencies · Environment & life safety | E · Potential harm Pattern | Corrected Apr 3, 2026 |
| Feb 6, 2026 | K-0918 | Have generator or other power source capable of supplying service within 10 seconds. Gas, Vacuum, and Electrical Systems Deficiencies · Environment & life safety | F · Potential harm Widespread | Corrected Apr 3, 2026 |
| Feb 6, 2026 | K-0920 | Ensure proper usage of power strips and extension cords. Gas, Vacuum, and Electrical Systems Deficiencies · Environment & life safety | D · Potential harm Isolated | Corrected Apr 3, 2026 |
| Feb 6, 2026 | K-0923 | Have proper medical gas storage and administration areas. Gas, Vacuum, and Electrical Systems Deficiencies · Environment & life safety | F · Potential harm Widespread | Corrected Apr 3, 2026 |
| Feb 6, 2026 | F-0582 | Give residents notice of Medicaid/Medicare coverage and potential liability for services not covered. Resident Rights Deficiencies · Resident rights & abuse/neglect | D · Potential harm Isolated | Corrected Mar 27, 2026 |
| Feb 6, 2026 | F-0600 | Protect each resident from all types of abuse such as physical, mental, sexual abuse, physical punishment, and neglect by anybody. Freedom from Abuse, Neglect, and Exploitation Deficiencies · Resident rights & abuse/neglect | E · Potential harm Pattern | Corrected Mar 27, 2026 |
| Feb 6, 2026 | F-0638 | Assure that each resident’s assessment is updated at least once every 3 months. Resident Assessment and Care Planning Deficiencies · Clinical care | E · Potential harm Pattern | Corrected Mar 27, 2026 |
| Feb 6, 2026 | F-0641 | Ensure each resident receives an accurate assessment. Resident Assessment and Care Planning Deficiencies · Clinical care | D · Potential harm Isolated | Corrected Mar 27, 2026 |
| Feb 6, 2026 | F-0695 | Provide safe and appropriate respiratory care for a resident when needed. Quality of Life and Care Deficiencies · Clinical care | D · Potential harm Isolated | Corrected Mar 27, 2026 |
| Feb 6, 2026 | F-0804 | Ensure food and drink is palatable, attractive, and at a safe and appetizing temperature. Nutrition and Dietary Deficiencies · Food, nutrition & hydration | E · Potential harm Pattern | Corrected Mar 27, 2026 |
| Feb 6, 2026 | F-0812 | Procure food from sources approved or considered satisfactory and store, prepare, distribute and serve food in accordance with professional standards. Nutrition and Dietary Deficiencies · Food, nutrition & hydration | E · Potential harm Pattern | Corrected Mar 27, 2026 |
| Dec 4, 2024 | F-0689 | Ensure that a nursing home area is free from accident hazards and provides adequate supervision to prevent accidents. Quality of Life and Care Deficiencies · Clinical care | L · Immediate jeopardy Widespread | Corrected Jan 17, 2025 |
| Dec 4, 2024 | F-0700 | Try different approaches before using a bed rail. If a bed rail is needed, the facility must (1) assess a resident for safety risk; (2) review these risks and benefits with the resident/representative; (3) get informed consent; and (4) Correctly install and maintain the bed rail. Quality of Life and Care Deficiencies · Clinical care | K · Immediate jeopardy Pattern | Corrected Jan 17, 2025 |
| Dec 4, 2024 | F-0686 | Provide appropriate pressure ulcer care and prevent new ulcers from developing. Quality of Life and Care Deficiencies · Clinical care | G · Actual harm Isolated | Corrected Jan 17, 2025 | Complaint |
| Dec 4, 2024 | E-0015 | Address subsistence needs for staff and patients. Emergency Preparedness Deficiencies · Emergency preparedness | E · Potential harm Pattern | Corrected Jan 24, 2025 |
| Dec 4, 2024 | K-0133 | Install a two-hour-resistant firewall separation. Construction Deficiencies · Environment & life safety | D · Potential harm Isolated | Corrected Feb 6, 2025 |
| Dec 4, 2024 | K-0211 | Keep aisles, corridors, and exits free of obstruction in case of emergency. Egress Deficiencies · Environment & life safety | D · Potential harm Isolated | Corrected Jan 27, 2025 |
| Dec 4, 2024 | K-0222 | Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements. Egress Deficiencies · Environment & life safety | D · Potential harm Isolated | Corrected Jan 27, 2025 |
| Dec 4, 2024 | K-0225 | Have stairways and smokeproof enclosures used as exits that meet safety requirements. Egress Deficiencies · Environment & life safety | D · Potential harm Isolated | Corrected Jan 25, 2025 |
| Dec 4, 2024 | K-0291 | Install emergency lighting that can last at least 1 1/2 hours. Egress Deficiencies · Environment & life safety | D · Potential harm Isolated | Corrected Feb 14, 2025 |
| Dec 4, 2024 | K-0293 | Have properly located and lighted "Exit" signs. Egress Deficiencies · Environment & life safety | D · Potential harm Isolated | Corrected Jan 27, 2025 |
| Dec 4, 2024 | K-0321 | Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system. Smoke Deficiencies · Environment & life safety | E · Potential harm Pattern | Corrected Feb 28, 2025 |
| Dec 4, 2024 | K-0324 | Provide properly protected cooking facilities. Smoke Deficiencies · Environment & life safety | E · Potential harm Pattern | Corrected Jan 24, 2025 |
| Dec 4, 2024 | K-0343 | Have a fire alarm with audible and visual signals that transmits the alarm automatically to notify emergency forces in event of fire. Smoke Deficiencies · Environment & life safety | D · Potential harm Isolated | Corrected Feb 14, 2025 |
| Dec 4, 2024 | K-0345 | Have approved installation, maintenance and testing program for fire alarm systems. Smoke Deficiencies · Environment & life safety | F · Potential harm Widespread | Corrected Feb 14, 2025 |
| Dec 4, 2024 | K-0353 | Inspect, test, and maintain automatic sprinkler systems. Smoke Deficiencies · Environment & life safety | E · Potential harm Pattern | Corrected Mar 3, 2025 |
| Dec 4, 2024 | K-0363 | Install corridor and hallway doors that block smoke. Smoke Deficiencies · Environment & life safety | D · Potential harm Isolated | Corrected Jan 27, 2025 |
| Dec 4, 2024 | K-0372 | Ensure smoke barriers are constructed to a 1 hour fire resistance rating. Smoke Deficiencies · Environment & life safety | E · Potential harm Pattern | Corrected Jan 27, 2025 |
| Dec 4, 2024 | K-0712 | Have simulated fire drills held at unexpected times. Miscellaneous Deficiencies · Environment & life safety | E · Potential harm Pattern | Corrected Jan 24, 2025 |
| Dec 4, 2024 | K-0761 | To conduct inspection, testing and maintenance of fire doors by qualified individuals. Miscellaneous Deficiencies · Environment & life safety | F · Potential harm Widespread | Corrected Jan 24, 2025 |
| Dec 4, 2024 | K-0781 | Have restrictions on the use of portable space heaters. Miscellaneous Deficiencies · Environment & life safety | E · Potential harm Pattern | Corrected Jan 25, 2025 |
| Dec 4, 2024 | K-0918 | Have generator or other power source capable of supplying service within 10 seconds. Gas, Vacuum, and Electrical Systems Deficiencies · Environment & life safety | F · Potential harm Widespread | Corrected Jan 24, 2025 |
| Dec 4, 2024 | K-0920 | Ensure proper usage of power strips and extension cords. Gas, Vacuum, and Electrical Systems Deficiencies · Environment & life safety | D · Potential harm Isolated | Corrected Jan 27, 2025 |
| Dec 4, 2024 | K-0921 | Ensure that testing and maintenance of electrical equipment is performed. Gas, Vacuum, and Electrical Systems Deficiencies · Environment & life safety | F · Potential harm Widespread | Corrected Jan 27, 2025 |
| Dec 4, 2024 | F-0565 | Honor the resident's right to organize and participate in resident/family groups in the facility. Resident Rights Deficiencies · Resident rights & abuse/neglect | D · Potential harm Isolated | Corrected Jan 17, 2025 |
| Dec 4, 2024 | F-0582 | Give residents notice of Medicaid/Medicare coverage and potential liability for services not covered. Resident Rights Deficiencies · Resident rights & abuse/neglect | D · Potential harm Isolated | Corrected Jan 17, 2025 |
| Dec 4, 2024 | F-0584 | Honor the resident's right to a safe, clean, comfortable and homelike environment, including but not limited to receiving treatment and supports for daily living safely. Resident Rights Deficiencies · Resident rights & abuse/neglect | F · Potential harm Widespread | Corrected Jan 17, 2025 | Complaint |
| Dec 4, 2024 | F-0656 | Develop and implement a complete care plan that meets all the resident's needs, with timetables and actions that can be measured. Resident Assessment and Care Planning Deficiencies · Clinical care | D · Potential harm Isolated | Corrected Jan 17, 2025 |
| Dec 4, 2024 | F-0679 | Provide activities to meet all resident's needs. Quality of Life and Care Deficiencies · Clinical care | D · Potential harm Isolated | Corrected Jan 17, 2025 |
| Dec 4, 2024 | F-0684 | Provide appropriate treatment and care according to orders, resident’s preferences and goals. Quality of Life and Care Deficiencies · Clinical care | D · Potential harm Isolated | Corrected Jan 17, 2025 | Complaint |
| Dec 4, 2024 | F-0761 | Ensure drugs and biologicals used in the facility are labeled in accordance with currently accepted professional principles; and all drugs and biologicals must be stored in locked compartments, separately locked, compartments for controlled drugs. Pharmacy Service Deficiencies · Medication management | E · Potential harm Pattern | Corrected Jan 17, 2025 |
| Dec 4, 2024 | F-0812 | Procure food from sources approved or considered satisfactory and store, prepare, distribute and serve food in accordance with professional standards. Nutrition and Dietary Deficiencies · Food, nutrition & hydration | F · Potential harm Widespread | Corrected Jan 17, 2025 |
| Dec 4, 2024 | F-0835 | Administer the facility in a manner that enables it to use its resources effectively and efficiently. Administration Deficiencies · Administration & records | F · Potential harm Widespread | Corrected Jan 17, 2025 | Complaint |
| Dec 4, 2024 | F-0921 | Make sure that the nursing home area is safe, easy to use, clean and comfortable for residents, staff and the public. Environmental Deficiencies · Environment & life safety | D · Potential harm Isolated | Corrected Jan 17, 2025 |
| Dec 4, 2024 | F-0940 | Develop, implement, and/or maintain an effective training program for all new and existing staff members. Administration Deficiencies · Administration & records | E · Potential harm Pattern | Corrected Jan 17, 2025 |
| Dec 4, 2024 | E-0004 | Develop and maintain an Emergency Preparedness Program (EP). Emergency Preparedness Deficiencies · Emergency preparedness | C · Minimal Widespread | Corrected Jan 24, 2025 |
| Dec 4, 2024 | E-0024 | Establish policies and procedures for volunteers. Emergency Preparedness Deficiencies · Emergency preparedness | C · Minimal Widespread | Corrected Jan 24, 2025 |
| Dec 4, 2024 | E-0037 | Establish staff and initial training requirements. Emergency Preparedness Deficiencies · Emergency preparedness | C · Minimal Widespread | Corrected Jan 24, 2025 |
| Dec 4, 2024 | F-0550 | Honor the resident's right to a dignified existence, self-determination, communication, and to exercise his or her rights. Resident Rights Deficiencies · Resident rights & abuse/neglect | C · Minimal Widespread | Corrected Jan 17, 2025 | Complaint |
| Dec 4, 2024 | F-0585 | Honor the resident's right to voice grievances without discrimination or reprisal and the facility must establish a grievance policy and make prompt efforts to resolve grievances. Resident Rights Deficiencies · Resident rights & abuse/neglect | C · Minimal Widespread | Corrected Jan 17, 2025 |
| Feb 24, 2023 | K-0211 | Keep aisles, corridors, and exits free of obstruction in case of emergency. Egress Deficiencies · Environment & life safety | E · Potential harm Pattern | Corrected Apr 10, 2023 |
| Feb 24, 2023 | K-0271 | Have exits that are accessible at all times. Egress Deficiencies · Environment & life safety | E · Potential harm Pattern | Corrected Apr 10, 2023 |
| Feb 24, 2023 | K-0321 | Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system. Smoke Deficiencies · Environment & life safety | D · Potential harm Isolated | Corrected Apr 10, 2023 |
| Feb 24, 2023 | K-0324 | Provide properly protected cooking facilities. Smoke Deficiencies · Environment & life safety | D · Potential harm Isolated | Corrected Apr 10, 2023 |
| Feb 24, 2023 | K-0345 | Have approved installation, maintenance and testing program for fire alarm systems. Smoke Deficiencies · Environment & life safety | D · Potential harm Isolated | Corrected Apr 10, 2023 |
| Feb 24, 2023 | K-0351 | Install an approved automatic sprinkler system. Smoke Deficiencies · Environment & life safety | D · Potential harm Isolated | Corrected Apr 10, 2023 |
| Feb 24, 2023 | K-0353 | Inspect, test, and maintain automatic sprinkler systems. Smoke Deficiencies · Environment & life safety | E · Potential harm Pattern | Corrected Apr 10, 2023 |
| Feb 24, 2023 | K-0355 | Properly select, install, inspect, or maintain portable fire extinguishes. Smoke Deficiencies · Environment & life safety | F · Potential harm Widespread | Corrected Apr 10, 2023 |
| Feb 24, 2023 | K-0363 | Install corridor and hallway doors that block smoke. Smoke Deficiencies · Environment & life safety | D · Potential harm Isolated | Corrected Apr 10, 2023 |
| Feb 24, 2023 | K-0531 | Have elevators that firefighters can control in the event of a fire. Services Deficiencies · Environment & life safety | D · Potential harm Isolated | Corrected Apr 10, 2023 |
| Feb 24, 2023 | K-0712 | Have simulated fire drills held at unexpected times. Miscellaneous Deficiencies · Environment & life safety | E · Potential harm Pattern | Corrected Apr 10, 2023 |
| Feb 24, 2023 | K-0918 | Have generator or other power source capable of supplying service within 10 seconds. Gas, Vacuum, and Electrical Systems Deficiencies · Environment & life safety | F · Potential harm Widespread | Corrected Apr 10, 2023 |
| Feb 24, 2023 | K-0920 | Ensure proper usage of power strips and extension cords. Gas, Vacuum, and Electrical Systems Deficiencies · Environment & life safety | D · Potential harm Isolated | Corrected Apr 10, 2023 |
| Feb 24, 2023 | F-0577 | Allow residents to easily view the nursing home's survey results and communicate with advocate agencies. Resident Rights Deficiencies · Resident rights & abuse/neglect | D · Potential harm Isolated | Corrected Mar 26, 2023 |
| Feb 24, 2023 | F-0638 | Assure that each resident’s assessment is updated at least once every 3 months. Resident Assessment and Care Planning Deficiencies · Clinical care | E · Potential harm Pattern | Corrected Apr 10, 2023 |
| Feb 24, 2023 | F-0812 | Procure food from sources approved or considered satisfactory and store, prepare, distribute and serve food in accordance with professional standards. Nutrition and Dietary Deficiencies · Food, nutrition & hydration | D · Potential harm Isolated | Corrected Apr 10, 2023 |
Reported from Payroll-Based Journal (PBJ) data, as published by CMS. Case-mix adjusted total: 3.77 (case-mix index 1.38).