| Severity | Isolated | Pattern | Widespread |
|---|---|---|---|
| Immediate jeopardy | J· | K1 | L· |
| Actual harm | G1 | H· | I· |
| Potential harm | D11 | E24 | F28 |
| Minimal | A· | B1 | C· |
CMS publishes about the three most recent standard surveys plus complaint and infection-control inspections from the prior three years. Older findings leave the dataset; their absence is not evidence they never happened.
Federal certification and the state license are different records. A nursing home is licensed by the state and, separately, certified by CMS to bill Medicare and/or Medicaid. We link them by the CCN when the state publishes it; otherwise by exact address, house number and street, or exact name within the same ZIP, and label that link as inferred. Never by name alone.
| Date | Domain | Survey types | Citations | Most severe | Open | |
|---|---|---|---|---|---|---|
| Dec 12, 2025 | Fire safety | Fire Safety Standard | 29 | Potential harm | — | Open → |
| Dec 12, 2025 | Health | Health Standard | 13 | Potential harm | — | Open → |
| Aug 23, 2024 | Fire safety | Fire Safety Standard | 6 | Immediate jeopardy | — | Open → |
| Aug 23, 2024 | Health | Health Standard | 9 | Actual harm | — | Open → |
| Jul 21, 2023 | Fire safety | Fire Safety Standard | 5 | Potential harm | — | Open → |
| Jul 21, 2023 | Health | Health Standard | 4 | Potential harm | — | Open → |
| Date | Type | Amount | Payment denial | Record |
|---|---|---|---|---|
| Aug 23, 2024 | Denial of payment for new admissions | — | Sep 25, 2024 · 9 days | 325104|Payment Denial|2024-09-25 |
| Aug 23, 2024 | Civil money penalty (fine) | $18,353 | — | 325104|Fine|93563 |
| Severity | Isolated | Pattern | Widespread |
|---|---|---|---|
| Immediate jeopardy | J· | K1 | L· |
| Actual harm | G1 | H· | I· |
| Potential harm | D11 | E24 | F28 |
| Minimal | A· | B1 | C· |
| Date | Tag | Deficiency | Scope / severity | Correction | Flags |
|---|---|---|---|---|---|
| Dec 12, 2025 | E-0006 | Conduct risk assessment and an All-Hazards approach. Emergency Preparedness Deficiencies · Emergency preparedness | F · Potential harm Widespread | Corrected Apr 2, 2026 | |
| Dec 12, 2025 | E-0009 | Include a process for Emergency Preparedness collaboration. Emergency Preparedness Deficiencies · Emergency preparedness | F · Potential harm Widespread | Corrected Apr 2, 2026 | |
| Dec 12, 2025 | E-0020 |
“Corrected” does not erase a citation: the historical finding stays listed with its disposition. Narrative statements of deficiencies are not part of the CMS dataset; see Care Compare for the official inspection report.
CMS ratings apply to CMS-certified nursing homes only and are relative within each state. They are not a guarantee of any individual resident’s experience.
CMS legal business name of the certified provider. Operates 3 facilities.
Not part of a CMS-reported chain.
| Name | Type | Role (Carefield group) | CMS role text | Share | Since |
|---|---|---|---|---|---|
| State of New Mexico | Organization | Operational / managerial control | OPERATIONAL/MANAGERIAL CONTROL | not provided | Aug 24, 2009 |
| Charles Jaramillo | Individual | Operational / managerial control | OPERATIONAL/MANAGERIAL CONTROL | not provided | Dec 1, 2008 |
| Charles Jaramillo | Individual | Managing employee | W-2 MANAGING EMPLOYEE | not provided | Dec 1, 2008 |
| Darlene Martinez | Individual | Managing employee | W-2 MANAGING EMPLOYEE | not provided | Apr 1, 2015 |
| Facility | Beds | CMS overall | Last inspection | Citations (window) | Fines |
|---|---|---|---|---|---|
| New Mexico State Veterans Home 992 South Broadway, Truth Or Consequences, NM 87901 CCN 325092 | 131 | Aug 13, 2026 | 662 harm5 open | $129k | |
| Fort Bayard Medical Center 41 Fort Bayard Road, Santa Clara, NM 88026 CCN 325120 |
Coordinates as published by CMS.
| Facility | Distance | Beds | CMS overall | Last inspection | Citations (window) | Fines |
|---|---|---|---|---|---|---|
| La Vida Buena Healthcare 2301 Collins Drive, Las Vegas, NM 87701 CCN 325065 | 2.3 km | 102 | Mar 10, 2026 | 893 harm11 open | $89k |
| Source | Record | Facts | Evidence | Source release | Retrieved |
|---|---|---|---|---|---|
| CMS Provider Information US-CMS | 325104 | name, address, phone, certification, certified_beds, ownership_type, legal_business_name, chain | Verified | Oct 1, 2026 | Nov 7, 2026 |
| CMS Provider Information US-CMS | 325104 | ratings, staffing, health_survey_score Five-Star ratings and PBJ staffing apply to the CMS-certified universe only. | Verified | Oct 1, 2026 | Nov 7, 2026 |
First seen by Carefield Nov 7, 2026 · last changed Nov 7, 2026. This record as JSON · Report a correction
| Establish policies and procedures including evacuation. Emergency Preparedness Deficiencies · Emergency preparedness |
| F · Potential harm Widespread |
| Corrected Apr 2, 2026 |
| Dec 12, 2025 | E-0031 | Provide emergency officials' contact information. Emergency Preparedness Deficiencies · Emergency preparedness | F · Potential harm Widespread | Corrected Apr 2, 2026 |
| Dec 12, 2025 | K-0100 | Meet other general requirements. Construction Deficiencies · Environment & life safety | F · Potential harm Widespread | Corrected May 8, 2026 |
| Dec 12, 2025 | K-0111 | Satisfy building requirements after a repair, renovation, modification, or change of user/occupancy. Construction Deficiencies · Environment & life safety | E · Potential harm Pattern | Corrected Apr 2, 2026 |
| Dec 12, 2025 | K-0211 | Keep aisles, corridors, and exits free of obstruction in case of emergency. Egress Deficiencies · Environment & life safety | E · Potential harm Pattern | Corrected Apr 2, 2026 |
| Dec 12, 2025 | K-0222 | Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements. Egress Deficiencies · Environment & life safety | E · Potential harm Pattern | Corrected May 27, 2026 |
| Dec 12, 2025 | K-0223 | Provide exit doors that are held open by devices that will automatically close on the activation of a fire alarm or smoke detector. Egress Deficiencies · Environment & life safety | E · Potential harm Pattern | Corrected Apr 2, 2026 |
| Dec 12, 2025 | K-0291 | Install emergency lighting that can last at least 1 1/2 hours. Egress Deficiencies · Environment & life safety | F · Potential harm Widespread | Corrected Apr 10, 2026 |
| Dec 12, 2025 | K-0293 | Have properly located and lighted "Exit" signs. Egress Deficiencies · Environment & life safety | E · Potential harm Pattern | Corrected Apr 2, 2026 |
| Dec 12, 2025 | K-0321 | Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system. Smoke Deficiencies · Environment & life safety | E · Potential harm Pattern | Corrected Apr 2, 2026 |
| Dec 12, 2025 | K-0324 | Provide properly protected cooking facilities. Smoke Deficiencies · Environment & life safety | F · Potential harm Widespread | Corrected Apr 2, 2026 |
| Dec 12, 2025 | K-0345 | Have approved installation, maintenance and testing program for fire alarm systems. Smoke Deficiencies · Environment & life safety | F · Potential harm Widespread | Corrected May 27, 2026 |
| Dec 12, 2025 | K-0346 | Follow proper procedures when the fire alarm was out of service for more than 4 hours. Smoke Deficiencies · Environment & life safety | F · Potential harm Widespread | Corrected May 22, 2026 |
| Dec 12, 2025 | K-0353 | Inspect, test, and maintain automatic sprinkler systems. Smoke Deficiencies · Environment & life safety | F · Potential harm Widespread | Corrected May 27, 2026 |
| Dec 12, 2025 | K-0354 | Follow proper procedures when the automatic sprinkler systems was out of service for more than 10 hours. Smoke Deficiencies · Environment & life safety | F · Potential harm Widespread | Corrected May 22, 2026 |
| Dec 12, 2025 | K-0355 | Properly select, install, inspect, or maintain portable fire extinguishes. Smoke Deficiencies · Environment & life safety | E · Potential harm Pattern | Corrected Apr 2, 2026 |
| Dec 12, 2025 | K-0363 | Install corridor and hallway doors that block smoke. Smoke Deficiencies · Environment & life safety | E · Potential harm Pattern | Corrected Apr 2, 2026 |
| Dec 12, 2025 | K-0372 | Ensure smoke barriers are constructed to a 1 hour fire resistance rating. Smoke Deficiencies · Environment & life safety | E · Potential harm Pattern | Corrected Apr 2, 2026 |
| Dec 12, 2025 | K-0374 | Install smoke barrier doors that can resist smoke for at least 20 minutes. Smoke Deficiencies · Environment & life safety | E · Potential harm Pattern | Corrected Apr 2, 2026 |
| Dec 12, 2025 | K-0511 | Have properly installed electrical wiring and gas equipment. Services Deficiencies · Environment & life safety | F · Potential harm Widespread | Corrected Apr 2, 2026 |
| Dec 12, 2025 | K-0712 | Have simulated fire drills held at unexpected times. Miscellaneous Deficiencies · Environment & life safety | F · Potential harm Widespread | Corrected May 27, 2026 |
| Dec 12, 2025 | K-0741 | Have posted "No-smoking" signs in areas where smoking is not permitted or ashtrays provided where smoking was allowed. Miscellaneous Deficiencies · Environment & life safety | F · Potential harm Widespread | Corrected May 27, 2026 |
| Dec 12, 2025 | K-0911 | Meet requirements for the installation and maintenance of electrical systems. Gas, Vacuum, and Electrical Systems Deficiencies · Environment & life safety | E · Potential harm Pattern | Corrected Apr 1, 2026 |
| Dec 12, 2025 | K-0914 | Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing. Gas, Vacuum, and Electrical Systems Deficiencies · Environment & life safety | F · Potential harm Widespread | Corrected Apr 20, 2026 |
| Dec 12, 2025 | K-0918 | Have generator or other power source capable of supplying service within 10 seconds. Gas, Vacuum, and Electrical Systems Deficiencies · Environment & life safety | F · Potential harm Widespread | Corrected May 27, 2026 |
| Dec 12, 2025 | K-0920 | Ensure proper usage of power strips and extension cords. Gas, Vacuum, and Electrical Systems Deficiencies · Environment & life safety | E · Potential harm Pattern | Corrected Apr 2, 2026 |
| Dec 12, 2025 | K-0923 | Have proper medical gas storage and administration areas. Gas, Vacuum, and Electrical Systems Deficiencies · Environment & life safety | E · Potential harm Pattern | Corrected Apr 14, 2026 |
| Dec 12, 2025 | F-0628 | Provide the required documentation or notification related to the resident's needs, appeal rights, or bed-hold policies. Resident Rights Deficiencies · Resident rights & abuse/neglect | D · Potential harm Isolated | Corrected Feb 2, 2026 |
| Dec 12, 2025 | F-0636 | Assess the resident completely in a timely manner when first admitted, and then periodically, at least every 12 months. Resident Assessment and Care Planning Deficiencies · Clinical care | D · Potential harm Isolated | Corrected Feb 2, 2026 |
| Dec 12, 2025 | F-0655 | Create and put into place a plan for meeting the resident's most immediate needs within 48 hours of being admitted Resident Assessment and Care Planning Deficiencies · Clinical care | D · Potential harm Isolated | Corrected Feb 2, 2026 |
| Dec 12, 2025 | F-0656 | Develop and implement a complete care plan that meets all the resident's needs, with timetables and actions that can be measured. Resident Assessment and Care Planning Deficiencies · Clinical care | D · Potential harm Isolated | Corrected Feb 2, 2026 |
| Dec 12, 2025 | F-0657 | Develop the complete care plan within 7 days of the comprehensive assessment; and prepared, reviewed, and revised by a team of health professionals. Resident Assessment and Care Planning Deficiencies · Clinical care | E · Potential harm Pattern | Corrected Feb 2, 2026 |
| Dec 12, 2025 | F-0658 | Ensure services provided by the nursing facility meet professional standards of quality. Resident Assessment and Care Planning Deficiencies · Clinical care | D · Potential harm Isolated | Corrected Feb 2, 2026 |
| Dec 12, 2025 | F-0685 | Assist a resident in gaining access to vision and hearing services. Quality of Life and Care Deficiencies · Clinical care | D · Potential harm Isolated | Corrected Feb 2, 2026 |
| Dec 12, 2025 | F-0728 | Ensure that nurse aides who have worked more than 4 months, are trained and competent; and nurse aides who have worked less than 4 months are enrolled in appropriate training. Nursing and Physician Services Deficiencies · Staffing & supervision | F · Potential harm Widespread | Corrected Feb 2, 2026 |
| Dec 12, 2025 | F-0730 | Observe each nurse aide's job performance and give regular training. Nursing and Physician Services Deficiencies · Staffing & supervision | E · Potential harm Pattern | Corrected Feb 2, 2026 |
| Dec 12, 2025 | F-0761 | Ensure drugs and biologicals used in the facility are labeled in accordance with currently accepted professional principles; and all drugs and biologicals must be stored in locked compartments, separately locked, compartments for controlled drugs. Pharmacy Service Deficiencies · Medication management | E · Potential harm Pattern | Corrected Feb 2, 2026 |
| Dec 12, 2025 | F-0806 | Ensure each resident receives and the facility provides food that accommodates resident allergies, intolerances, and preferences, as well as appealing options. Nutrition and Dietary Deficiencies · Food, nutrition & hydration | D · Potential harm Isolated | Corrected Feb 2, 2026 |
| Dec 12, 2025 | F-0835 | Administer the facility in a manner that enables it to use its resources effectively and efficiently. Administration Deficiencies · Administration & records | F · Potential harm Widespread | Corrected Feb 2, 2026 |
| Dec 12, 2025 | F-0842 | Safeguard resident-identifiable information and/or maintain medical records on each resident that are in accordance with accepted professional standards. Resident Assessment and Care Planning Deficiencies · Clinical care | D · Potential harm Isolated | Corrected Feb 2, 2026 |
| Aug 23, 2024 | K-0111 | Satisfy building requirements after a repair, renovation, modification, or change of user/occupancy. Construction Deficiencies · Environment & life safety | K · Immediate jeopardy Pattern | Corrected Oct 4, 2024 |
| Aug 23, 2024 | F-0600 | Protect each resident from all types of abuse such as physical, mental, sexual abuse, physical punishment, and neglect by anybody. Freedom from Abuse, Neglect, and Exploitation Deficiencies · Resident rights & abuse/neglect | G · Actual harm Isolated | Corrected Oct 4, 2024 |
| Aug 23, 2024 | K-0211 | Keep aisles, corridors, and exits free of obstruction in case of emergency. Egress Deficiencies · Environment & life safety | E · Potential harm Pattern | Corrected Oct 4, 2024 |
| Aug 23, 2024 | K-0222 | Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements. Egress Deficiencies · Environment & life safety | F · Potential harm Widespread | Corrected Oct 4, 2024 |
| Aug 23, 2024 | K-0324 | Provide properly protected cooking facilities. Smoke Deficiencies · Environment & life safety | F · Potential harm Widespread | Corrected Oct 4, 2024 |
| Aug 23, 2024 | K-0353 | Inspect, test, and maintain automatic sprinkler systems. Smoke Deficiencies · Environment & life safety | F · Potential harm Widespread | Corrected Oct 4, 2024 |
| Aug 23, 2024 | K-0712 | Have simulated fire drills held at unexpected times. Miscellaneous Deficiencies · Environment & life safety | F · Potential harm Widespread | Corrected Oct 4, 2024 |
| Aug 23, 2024 | F-0609 | Timely report suspected abuse, neglect, or theft and report the results of the investigation to proper authorities. Freedom from Abuse, Neglect, and Exploitation Deficiencies · Resident rights & abuse/neglect | D · Potential harm Isolated | Corrected Oct 4, 2024 |
| Aug 23, 2024 | F-0686 | Provide appropriate pressure ulcer care and prevent new ulcers from developing. Quality of Life and Care Deficiencies · Clinical care | E · Potential harm Pattern | Corrected Oct 4, 2024 |
| Aug 23, 2024 | F-0689 | Ensure that a nursing home area is free from accident hazards and provides adequate supervision to prevent accidents. Quality of Life and Care Deficiencies · Clinical care | E · Potential harm Pattern | Corrected Oct 4, 2024 |
| Aug 23, 2024 | F-0804 | Ensure food and drink is palatable, attractive, and at a safe and appetizing temperature. Nutrition and Dietary Deficiencies · Food, nutrition & hydration | E · Potential harm Pattern | Corrected Oct 4, 2024 |
| Aug 23, 2024 | F-0806 | Ensure each resident receives and the facility provides food that accommodates resident allergies, intolerances, and preferences, as well as appealing options. Nutrition and Dietary Deficiencies · Food, nutrition & hydration | E · Potential harm Pattern | Corrected Oct 4, 2024 |
| Aug 23, 2024 | F-0812 | Procure food from sources approved or considered satisfactory and store, prepare, distribute and serve food in accordance with professional standards. Nutrition and Dietary Deficiencies · Food, nutrition & hydration | F · Potential harm Widespread | Corrected Oct 4, 2024 |
| Aug 23, 2024 | F-0825 | Provide or get specialized rehabilitative services as required for a resident. Quality of Life and Care Deficiencies · Clinical care | E · Potential harm Pattern | Corrected Oct 4, 2024 |
| Aug 23, 2024 | F-0947 | Ensure nurse aides have the skills they need to care for residents, and give nurse aides education in dementia care and abuse prevention. Nursing and Physician Services Deficiencies · Staffing & supervision | E · Potential harm Pattern | Corrected Oct 4, 2024 |
| Jul 21, 2023 | K-0321 | Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system. Smoke Deficiencies · Environment & life safety | F · Potential harm Widespread | Corrected Nov 1, 2023 |
| Jul 21, 2023 | K-0343 | Have a fire alarm with audible and visual signals that transmits the alarm automatically to notify emergency forces in event of fire. Smoke Deficiencies · Environment & life safety | F · Potential harm Widespread | Corrected Aug 31, 2023 |
| Jul 21, 2023 | K-0372 | Ensure smoke barriers are constructed to a 1 hour fire resistance rating. Smoke Deficiencies · Environment & life safety | F · Potential harm Widespread | Corrected Nov 1, 2023 |
| Jul 21, 2023 | K-0712 | Have simulated fire drills held at unexpected times. Miscellaneous Deficiencies · Environment & life safety | F · Potential harm Widespread | Corrected Aug 10, 2023 |
| Jul 21, 2023 | K-0918 | Have generator or other power source capable of supplying service within 10 seconds. Gas, Vacuum, and Electrical Systems Deficiencies · Environment & life safety | F · Potential harm Widespread | Corrected Oct 19, 2023 |
| Jul 21, 2023 | F-0689 | Ensure that a nursing home area is free from accident hazards and provides adequate supervision to prevent accidents. Quality of Life and Care Deficiencies · Clinical care | D · Potential harm Isolated | Corrected Aug 10, 2023 |
| Jul 21, 2023 | F-0695 | Provide safe and appropriate respiratory care for a resident when needed. Quality of Life and Care Deficiencies · Clinical care | E · Potential harm Pattern | Corrected Aug 10, 2023 |
| Jul 21, 2023 | F-0760 | Ensure that residents are free from significant medication errors. Pharmacy Service Deficiencies · Medication management | D · Potential harm Isolated | Corrected Aug 10, 2023 |
| Jul 21, 2023 | F-0880 | Provide and implement an infection prevention and control program. Infection Control Deficiencies · Infection prevention | B · Minimal Pattern | Corrected Aug 10, 2023 |
Reported from Payroll-Based Journal (PBJ) data, as published by CMS. Case-mix adjusted total: 5.97 (case-mix index 1.06).
| 200 |
| Aug 13, 2026 |
1071 IJ1 harm12 open |
| $84k |